Record Plus circuit breakers are designed to protect, isolate and switch circuits in low voltage distribution networks. Circuit protection is provided by a combination of the devices unique current limiting properties and integrated protection devices commonly referred to as trip units.
Features
Rated at 160 and 250A, the FE frame sizes are designed for side-by-side mounting with FD63/160 types in panels.
FE sizes are equipped with an easily accessible busbar connection and can also be supplied with cable lugs for use with copper or aluminum conductors.
The design allows the use of interchangeable thermal-magnetic, magnetic-only, and electronic trip units.
LTM | Line thermal magnetic protection
- Has no thermal setting option and a magnetic release set at 10 x In.(1)
LTMD | Selective thermal magnetic protection
- Has a thermal setting of 0.8 to 1 times and a magnetic release set at 10(1) x the selected rating. Designed for the protection of generic loads
GTM | Generator thermal magnetic protection
- A trip unit offering selectivity with downstream devices as the ElfaPlus MCBs and Surion motor starter. Has a thermal setting of 0.8 to 1 times, and a magnetic release set at 10(1) x the selected rating
Mag Break | Magnetic Only protection
- A trip unit designed to offer short-circuit protection only and specifically suited for motor protection in coordination with a contactor and a thermal relay (EN 60947-4)
SMR1 | Selective electronic trip unit
- The SMR1 range is designed for simplicity and includes numerous exciting features as an overload signalling option, a built-in temperature sensor and rating plugs suitable for both line and motor protection.
|


|
Breaking Capacities / Protection
| Icu 400/415V AC in kA eff. |
| Type | V | N | H | L |
| FE160 | | 50 | 80 | 150 |
| FE250 | 36 | 50 | 80 | 150 |
| |
Trip Unit | Rated Current (A) | LTM | LTMD | GTM | Mag Break | SMR1 |
| | 3 | | | | N, H, L | |
| | 7 | | | | N, H, L | |
| | 12.5 | | | | N, H, L | |
| | 20 | | | | N, H, L | |
| | 25 | N, H, L | | | | N, H, L |
| | 30 | | | | N, H, L | |
| | 32 | N, H, L | | | | |
| FE160 | 40 | N, H, L | | | | |
| | 50 | N, H, L | | | N, H, L | |
| | 63 | N, H, L | | | | N, H, L |
| | 80 | N, H, L | | | N, H, L | |
| | 100 | N, H, L | N, H, L | N, H, L | N, H, L | |
| | 125 | N, H, L | N, H, L | N, H, L | N, H, L | N, H, L |
| | 160 | N, H, L | N, H, L | N, H, L | N, H, L | N, H, L |
| | 125 | | N, H, L | | | N, H, L |
| FE250 | 160 | V | N, H, L | N, H, L | N, H, L | N, H, L |
| | 200 | V | N, H, L | N, H, L | N, H, L | |
| | 250 | V | N, H, L | N, H, L | N, H, L | N, H, L |
Dimensions
| Dimensional Drawings - Breakers - FD63/160 fixed, front connected |
 |
|