Series CL - Three and four pole minicontactors

 

Product Brochures

Product Catalogues

Contact GE

Features

  • Control circuit: Alternating current up to 690V
    Direct current up to 440V
  • Terminal numbering in accordance with EN 50005 and EN 50012
  • Fixing by clipping onto 35mm DIN rail EN 50022-35 or by screws
  • Screws protected against accidental contact in accordance with VDE 0106 T.100, VBG4.
  • Ring terminal version
  • Three coil terminals
  • Mounting possibilities of front/side instantaneous auxiliary contact blocks, timed auxiliary contact blocks, mechanical latch, transient suppressor block and interface modules
  • Degree of protection: IP20 to CL00 ... CL02
    IP10 to CL25 ... CL10
  • Maximum number of auxiliary contacts: 4 for CL00 ... CL25
    6 for CL04 ... CL45
    8 for CL06 ... CL10

 

 

Series CL - Three and four pole minicontactors

Where To Buy

Technical Data

 

Power circuit
  CL00 CL01 CL02 CL25 CL03 CL04 CL45 CL05 CL06 CL07 CL08 CL09 CL10
Three pole version
Rated thermal current @ Ø <= 55°C (A) 25 25 32 45 45 60 60   90 110 110 140 140
Rated operational current @ AC-3 (A) 9 12 18 25 25 32 40   50 65 80 95 105
Rated operational voltage Ue (V) 690 690 690 690 690 690 690   690 690 690 690 690
Four pole version (4NO and 2NO+2NC)
Rated thermal current @ Ø <= 55°C (A)   25 32   45 60   90   110 110 140  
Rated operational voltage Ue (V)   690 690   690 690   690   690 690 690  
Three and four pole version
Rated insulation voltage Ui (V) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Maximum continuous current AC-1 (A) 25 25 32 45 45 60 60 90 90 110 110 140 140
Frequency limits (Hz) 25-400 25-400 25-400 25-400 25-400 25-400 25-400 25-400 25-400 25-400 25-400 25-400 25-400
Making capacity (RMS) (IEC 947) (A) 450 450 450 450 550 550 550 1000 1000 1000 1000 1280 1280
Breaking capacity (RMS) (IEC 947)
Ue <= 400V (A) 250 250 250 350 450 450 450 920 920 920 920 1050 1050
Ue = 500V (A) 250 250 250 320 450 450 450 920 920 920 920 1050 1050
Ue = 690V (A) 130 130 130 170 205 205 205 780 780 780 780 950 950
Short Time Current
5 sec. (A)2052052542804504504505657101130113014851485
10 sec.(A)14414418020032032040050050080080010501050
30 sec.(A)8585104115185185230290290460460600600
1 min.(A)60607480130130165205205325325430430
3 min.(A)353546509090100120120185185250250
Recovery time (min.)10101010101010101010101010
Protec. against short-circuit with fuses without TOR
gL/gG (A)50506363100100125200200200200250250
gL-gG (A)25353550636380100100125125160200
gL-gG (A)101025353535508080100100140160
Impedance per pole (mΩ)2.352.352.411.651.281.280.950.850.850.860.860.760.76
Power dissipation per pole
AC-1 (W)1.471.472.463.342.594.63.426.896.8610.410.414.8914.89
AC-3 (W)0.190.340.781.030.81.311.521.362.123.635.56.868.37
Insulation resistance
Between adjacent poles (mΩ)>10>10>10>10>10>10>10>10>10>10>10>10>10
Between poles and earth (mΩ)>10>10>10>10>10>10>10>10>10>10>10>10>10
Between input and output (mΩ)>10>10>10>10>10>10>10>10>10>10>10>10>10

 

Dimensions

 

Dimensional Drawings - Three and four pole minicontactors
Dimensional Drawings - Screw terminalDimensional Drawings - Ring terminal
Screw terminalRing terminal