The SG Series is one of the best performing and most reliable three-phase UPS systems providing critical power protection for a wide range of applications. Every SG Series system operates in VFI mode (Voltage Frequency Independent) yielding the maximum levels of power reliability for all mission-critical processes. The SG Series was developed using GE's Design for Six Sigma methodology to ensure that the product fully meets customer requirements and expectations.
Features
- Voltage Frequency Independent (VFI) operation fully compliant with international standards (IEC 62040-3) providing full power protection for demanding critical applications
- Front access for all service and maintenance reducing operational footprint
- RS232 communication for advanced communication between UPS and PC
- Excellent dynamic response preventing the need for oversizing in case of pulsating loads
- Superior Battery Management (SBM) enhances battery lifetime resulting in reduced cost of operation
- Super ECO Mode (user selectable) to reduce energy consumption costs
- Automatic start-up procedure and user friendly interface simplifying UPS operation
- Maintenance bypass integrated in UPS cabinet, no need for external switches
- Redundant cooling fans for highest reliability
- Output power factor 0.9 prevents need to oversize in case of power factor corrected loads
- Low input current harmonics with integrated filter (optional)
|

|
Technical Specifications
Topology : VFI (Voltage Frequency Independent) according to IEC 62040-3
Technology : IGBT and DSP (Digital Signal Processor)
Operating Modes : Double conversion, automatic bypass, super ECO mode, frequency converter, RPA up to 8 units
Output power rating (kVA) (at PF = 0.6-0.9 lagging) | 80 | 100 | 120 | 160* | 200* |
| Output power rating (kW) | 72 | 90 | 108 | 144 | 180 |
| Output power factor | 0.9 |
| Dimensions (w x d x h), mm | 800x800x1820 | 1200x800x1820 | 1650x800x1820 |
| Weight (kg) (160/200 kVA preliminary) | 605 | 830 | 830 | 1100 | 1300 |
| Audible noise | <65 db(A) |
| System efficiency | 98% on super ECO mode |
| Protection degree | IP 20 |
| Input voltage range | 320 - 460 Vac |
| Input frequency range | 45 - 65 Hz |
| Input current THD | < 6% (optional) | < 5% (optional) |
| Output voltage | 3x380/400/415Vac, user selectable |
| Output frequency | 50/60 Hz +/- 0.01% |
| Output voltage THD at linear load | < 1% |
| Output voltage THD at non-linear load | < 3% |
| Output voltage regulation static | < +/- 1% |
Output voltage regulation dynamic (100% step load) | < +/- 2% (recovery time < 20 ms) |
| Overload capability on inverter | 125% 10 min., 150% 1 min. |
| Ambient operating temperature | 0 - 40 °C |
| Colour | RAL 9003, white |
| Safety standards | EN/IEC 62040-1-1 |
| EMC standards | EN/IEC 62040-2 UPS of category C2 optional (Class A) |
Specifications subject to change without prior notice
|