Uninterruptible Power Supply (UPS) - On-line LP 11U UPS

 

Product Brochures

Product Catalogues

Contact GE

The LP Series UPS is a true on-line double conversion, intelligent and heavy-duty UPS for centralized power protection. The continuous operation technology with isolated bypass provides the highest reliability against utility disturbances under the toughest conditions. The LP UPS is easy to install and service. It can be integrated into any office or industrial environment.

Thanks to RPA™ (Redundant Parallel Architecture™) the system power can be expanded by paralleling units or the system reliability can be increased by adding redundant units. The LP 11U are single phase UPS for 208/230/240 Volt in, the LP 11U/120 models are for 120 Volt 1-phase in. All models have outputs for 120V, 208 and 230/240 Volt single phase.

Features

  • Isolation transformer | The output of the output converter can be galvanically isolated from the utility. The neutral of the UPS output is internally connected to the input neutral. The output is totally isolated if the bypass circuit breaker is disconnected
  • Bypass enable/disable | If you do not want the automatic bypass switch to transfer to bypass, e.g. in situations of very bad or unstable utility, the bypass switch can be disabled. This feature is essential if the UPS is used as a frequency converter
  • Frequency tracking range | The output frequency will follow the bypass frequency within the frequency tracking range (standard ± 2%). If the bypass frequency is outside these limits, the inverter will run on its internal oscillator, and bypass transfer is inhibited. If you want the bypass switch to operate over a wider frequency range (e.g. in case of generator supply), the tracking range can be changed into ± 4% or ± 6%
  • ECO-Mode | The LP UPS is equipped with the ECO-Mode feature. If the feature is enabled, the load is operated on utility through the electronic bypass switch. If the utility is interrupted or out of limits the load is automatically transferred to the inverter. Operating the load on utility improves the efficiency of the UPS and saves on energy costs. As the unit produces less heat in ECO-Mode, also the energy costs of an airco installation will be reduced. We advise not to use the ECO-Mode in case of an unstable utility
  • Communications port | 9-pin Sub-D female plug (RS232/contact interface)
  • Auto restart | If this feature is enabled and the unit has shut down (e.g. due to overload) the UPS will start up automatically when the normal situation is restored. The factory setting is: enabled. If the auto restart feature is disabled the unit will not automatically restart when the normal situation is restored
  • Service warning | The LP UPS can generate a service warning periodically. The period can be set to 28, 24, 20, 16, 12 or 8 months. Default the service warning is disabled
  • Event logging | The LP UPS stores the 200 last events in its memory. The service engineer can use this information for quick and accurate diagnostics. The event list contains all events like alarms, error and status messages

 

 

Uninterruptible Power Supply (UPS) - On-line LP 11U UPS

 

Technical Specifications

 

LP 11U model   5-11U 6-11U 8-11U 10-11U
Enclosure  
Construction sheet steel cubicle and ABS
Colour front: RAL 9006 (aluminum) cabinet: RAL 9010 (white)
Protection IP 20
Dimensions  
LP 11U  
Cabinet type VSD2
Dimensions (hxwxd, mm / inch) 680 x 313 x 730 / 26.8 x 12.3 x 28.7
Shipping dims (hxwxd, mm / inch) 915 x 460 x 810 / 36 x 18.1 x 31.9
LP 11U/120  
Cabinet type VSD2+VSDT2n.a.n.a.
Dimensions (hxwxd, mm / inch) 995 x 313 x 730 / 39.2 x 12.3 x 28.7
Shipping dims (hxwxd, mm / inch) 1260 x 460 x 810 / 49.6 x 18.1 x 31.9
Weight  
LP 11U  
Weight (kg / lbs) 134 / 295134 / 295175 / 385186 / 410
Shipping weight (kg / lbs) 150 / 330150 / 330200 / 440210 / 462
LP 11U/120  
Weight (kg / lbs) 175 / 385175 / 385  
Shipping weight (kg / lbs) 200 / 440200 / 440  
Ratings  
Output rating (kVA / kW) 5 / 46 / 4.88 / 6.410 / 8
Input  
Nominal AC input voltage 208 - 240 V or 120 V
AC input voltage range   
at 100% load 162 - 285 V81 - 141 V
at 70% load 146 - 285 V72 - 141 V
at 25% load 132 - 285 V66.5 - 141 V
Input frequency range 40-70 Hz
Input current waveform sinusoidal
Input power factor ≥ 0.99
THD input current ≤ 10%
Inrush current none
DC output voltage 380 V
Input currents (Amps)@ 120V 43.350.8--
(Amps)@ 208V 253040.550.3
(Amps)@ 240V 21.425.134.842
Output  
Output power at pf. = 0.8, VA* 50006000800010000
at nominal AC input voltage, W     
Semiconductor IGBT
AC output voltage 120 / 208 / 240 Volt ± 1% static resistive load
  120 / 208 / 240 Volt ± 2% measured crest load 2.5:1
  120 / 208 / 240 Volt ± 2% dynamic mean deviation over one half cycle
  for 100% of rated load applied or removed
Typical overload 110% ≥ 20 minutes
(temp. dependent) 130% ≥ 3.5 minutes
  150% ≥ 2 minutes
Short circuit current, A (240ms) 45506775
Output frequency 50 or 60 Hz selectable, ± 0.1%, unless synchronized with the utility
Freq. tracking range ± 2/4/6% of nominal (user selectable)
Output waveform sine wave
Max. phase difference input-output 
Harmonic distortion 2% max. with linear load
Power factor range Any lagging or leading power factor is permitted within the specified rating to pf. 0.5
Output derating altitude Till 1000m (3280 ft) no derating
  Above 1000m (3280 ft) 12.5% per 1000m, max. 4000m (13,000 ft)
Protection Automatic shut down (or transfer to bypass, if bypass is available) in case of
  - low/high DC voltage
  - overtemperature
  - overload / short circuit
  The output is protected against connection to the utility
Bypass  
Bypass voltage limits - 15 % + 10% of nominal
Transfer transients >typically 2% mean deviation over one half cycle.
Frequency tracking range ± 2/4/6% of nominal (user selectable)
Slew rate max. 1Hz/sec or 5Hz/sec (user selectable)

 

Runtime Table

LP 11U model5-11U6-11U8-11U10-11U
Runtimes (ratings given for 25°C / 77°F)
VA / Wattsruntime in minutes
1000 / 8006262112112
2000 / 160030305757
3000 / 240014143737
5000 / 4000992020
6000 / 4800-71616
8000 / 6400--1010
10000 / 8000---7

 

Units connected to battery extension packs will have longer runtimes