| Nominal current rating (A) |
25 |
40 |
63 |
100 |
150 |
250 |
400 |
630 |
800 |
1000 |
| Enclosures |
| 1-pole, Stand Alone * |
G |
A |
B |
- |
| 1-pole, 19 inch rackmount * |
H* |
- |
| 2-pole, Stand Alone * |
G |
A |
B |
- |
| 2-pole, 19 inch rackmount * |
H* |
- |
| 3-pole, floorstanding cabinet * |
A |
B |
C |
F |
J |
| 3-pole, 19 inch rackmounted * |
E |
- |
| 4-pole, floorstanding cabinet * |
A |
B |
C |
F |
J |
| 4-pole, 19 inch rackmount * |
E |
- |
| Weight (kg), only for 3- and 4-pole (preliminary) |
60 |
68 |
72 |
195 |
195 |
195 |
280 |
280 |
350 |
380 |
| Colour |
RAL 7032 |
| Input characteristics |
| Nominal input voltage |
400V ph-ph / 230V ph-N |
| Input voltage window |
-25% / +20% |
| Nominal frequency |
50Hz |
| Frequency window |
-9% / +6% |
| Output characteristics |
| Efficiency |
> 99% at cos phi 0.8 |
| Crest factor acceptance |
3.5 |
| Power factor (max. Cos phi) |
0.5 - 1.0 (leading/lagging) |
| Overload behaviour |
1 hour, 5 sec, 400 ms, 200 ms, 20 ms |
| Short circuit current withstand, kA (max 20 ms) |
3.2 |
8 |
15 |
22.5 |
39 |
46 |
55 |
| Transfer time (manual triggering) |
< 0.1 ms |
| Transfer time (automatic transfer) |
< 6 ms, typical: 3 ms |
| Settings |
| Overvoltage level setting |
+ 6/9/13/16/20%, selectable by dipswitch |
| Undervoltage level setting |
8/12/16/24%, selectable by dipswitch |
| Phase delay limit (for synchronised sources) |
8/12/16/20/24 degrees, selectable by dipswitch |
| Transfer blocked after output current exceeding limit |
no blocking, 3/4.5/6/7.5/9 x nominal current, selectable by dipswitch |
| Transfer time (sources not synchronised) |
13/17/25/50 ms, selectable by dipswitch |
| Delay for retransfer to preferred source |
0.8/1/8/25 sec, selectable by dipswitch |
| Ambient conditions |
| Operating temperature |
0 - 40 °C |
| Humidity |
< 95%, non-condensing |
| Altitude |
1000 m (above 1000 m 5% derating per 500 m; max. 3000 m) |
| Cooling |
redundant cooling fans |
| Audible noise |
< 55 db(A) |
| EMC |
EN 50022 level B, EN 60555-2-3 |
| Protection |
IP 20 (floorstanding), IP 00 (for rackmounted models) |
| Alarm / Status Contacts |
| Dry contacts |
300 Vdc or 250 Vac / 0.3 Adc or 4 Aac at 220V |
| Status information |
manual transfer on, retransfer off, primary/secondary source OK, primary/secondary source on |
| Disturbance alarms |
primary/secondary source not healthy, sources not synchronized, manual control on |
| Failure alarms |
overload, overtemperature, fuse failure, internal STS failure |