The SitePro family of high-performance UPS systems provides critical power protection for a range of applications. All SitePro models operate in a double conversion mode (providing true on-line operation), thus providing the highest levels of power reliability. Each UPS is fully compliant with international standards regarding Voltage Frequency Independent (VFI) operation. True VFI technology makes the GE SitePro an extremely reliable UPS for data security and other demanding critical applications.
This continuous on-line UPS is available in models from 10 kVA up to 500 kVA. For high-power redundant applications, the GE SitePro can be installed with up to eight units in parallel, achieving power protection up to 4 MVA.
Features
- High output power factor eliminates need for UPS oversizing
- Constant high efficiency at full and partial load
- Superior Battery Management (SBM) to enhance battery life and to prevent battery failure
- Super ECO Mode for energy savings
- Extremely low output distortion even at non-linear loads
- Highest levels of reliability and flexibility with Redundant Parallel Architecture (RPA)
- Best in class for variable load applications
- Various operation modes: double conversion; voltage and frequency stabilizer; frequency converter
- Galvanic isolation which provides additional critical power protection
- UPS monitoring and protection software
- Backfeed protection standard included providing a safe work environment
|

|
Technical Specifications
Topology : True on-line, double conversion (VFI) with integral static switch and internal service bypass
Technology : Advanced IGBT with SVM strategy, microprocessor controlled at optimal switching frequency
Operating Modes : True on-line double conversion, Super ECO Mode, voltage and frequency stabilizer, frequency converter, RPA up to 8 units
| Output power rating (kVA) |
10 |
15 |
20 |
30 |
40 |
60 |
80* |
100* |
120* |
150** |
200** |
250 |
300 |
400 |
500 |
| Output power factor |
1 |
1 |
1 |
1 |
1 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
| Output power rating (kW) |
10 |
15 |
20 |
30 |
40 |
54 |
72 |
90 |
108 |
135 |
180 |
225 |
270 |
360 |
450 |
| Dimensions (w x d x h, mm) |
680x800x1450 |
*** |
1100x800x1450 |
1100x800x1800 |
1550x800x1800 |
2600x800x1800 |
| Input voltage |
3x380/400/415Vac + N |
| Input frequency |
50/60 Hz +/- 10% |
| Output voltage (sinusoidal) |
3x380/400/415Vac + N |
| Output frequency |
50/60 Hz |
| Output distortion at linear load |
< 2% |
| Output distortion at non-linear load |
< 3% |
| Crest factor |
> 3:1 |
| Overload capability on inverter |
125% 10 min., 150% 1 min. (400-500 kVA 30 sec.) |
| Output voltage regulation |
|
| - static |
+/-1% |
| - dynamic |
+/-3% |
| Efficiency |
|
| - double conversion mode |
up to 94.5% |
| - Super ECO mode |
up to 98% |
| Backfeed protection |
standard |
| Ambient operating temperature |
0 - 40 °C (32-104 °F) |
| Colour |
RAL 9010, white |
| Protection degree |
IP 20 |
| EMC standards |
EN 50091-2 / IEC 62040-2 |
| Standard interfaces |
RS232; 6 programmable alarm contacts |
* These models will be replaced by SG Series UPS
** These models will be replaced by SG Series UPS
*** = 750x800x1450
Runtime Table
| SitePro UPS | 10kVA | 15kVA | 20kVA | 30kVA | 40kVA | 60kVA |
| Capacity of battery set (V/Ah) | | | | | | |
| 360/10 | 8 | - | - | - | - | - |
| 360/17 | 15 | 10 | 6 | - | - | - |
| 360/24 | 30 | 15 | 10 | 6 | - | - |
| 360/33 | 43 | 24 | 16 | 10 | 6 | - |
| 360/38 | 50 | 30 | 20 | 12 | 7 | - |
| 360/65 | 100 | 60 | 40 | 25 | 17 | 10 |
| 360/76 | 120 | 70 | 50 | 30 | 20 | 12 |
* For the full SitePro range (10-500 kVA) runtimes are possible from 5 minutes up to 4 hours.
|